a. In PROGRAM mode, navigate to: LEVEL METER> DIAGNOSTICS> ECHO PROFILES (3.1)
b. Press RIGHT arrow to request a profile.
c. In the Profile screen, press UP arrow to select the Transmit icon, and Right arrow to
update the profile.
d. Press DOWN arrow to select the Exit icon, then Right arrow to return to previous menu.
6.2.3.11 Device address
The default address for the device is 0. To reset the address via the handheld programmer,
see Device Reset (Page 111)
6.2.3.12 Auto false echo suppression
If SITRANS LR260 displays a false high level, or the reading is fluctuating between the correct
level and a false high level, you can use the Auto False Echo Suppression parameters to
prevent false echo detection. See TVT (Auto False Echo Suppression) setup (TVT SETUP)
(Page 86) for instructions.
Commissioning
6.2 Local commissioning