Operating Instructions

Table Of Contents
P
P
Low calibration point
Level
High calibration point
Sensor reference point
SITRANS LR260
Fill rate = 0.09 m/minute (Low Cal Pt. minus High Cal Pt.) / fastest fill/empty time
= (16 m – 0.5 m) / 180 min.
= 15.5 m /180 min. = 0.09 m/min.
Quick start setting Description
APPLICATION (Page 74) STEEL
RESPONSE RATE
(Page 74)
SLOW Response rate = 0.1 m/minute.
UNITS (Page 75) m
OPERATION (Page 75) LEVEL Material level referenced from Low Calibration Point.
LOW CALIBRATION POINT
(Page 76)
16 Process empty level.
HIGH CALIBRATION POINT
(Page 77)
0.5 Process full level.
APPLY? (Page 77)
(CHANGES)
YES Save new settings.
Commissioning
6.3 Application examples
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD 57