Double click on each axis and record the Xscale and Data Scale values, so that you can
restore the default view by resetting to these values.
You can save a profile or delete a saved profile.
After saving a profile, open menu View – Echo profile.
7.1.5.4 Trend
Note
Double click on each axis and record the Xscale and Data Scale values, so that you can restore
the default view by resetting to these values.
Open the menu View – Trend.
7.1.5.5 Auto false echo suppression
Note
If possible, adjust Auto False Echo Suppression parameters with an empty or almost empty
vessel. There should be a minimum distance of two meters from the radar instrument to the
material.
Set Auto False Echo Suppression and Auto Suppression Range during installation, if
possible.
Before adjusting these parameters, rotate the instrument for best signal (minimum false-
echo amplitude).
Operating
7.1 Operating via SIMATIC PDM
SITRANS LR260 with mA/HART
66 Operating Instructions, 11/2019, A5E32337683-AD