Use Device Reset to reset all user parameters excluding device addresses, the parameter
block Identification, and Maintenance Schedule parameters to the default settings.
1. Open the menu Device - Device Reset and click on OK to perform a reset to Factory
Defaults.
2. After the reset is complete, upload parameters to the PC/PG.
Note
If you are performing a reset after replacing the device with a different instrument, do not upload
parameters to the PC/PG.
7.1.5.11 Configuration flag reset
To reset the configuration flag to zero, open the menu Device Configuration Flag Reset and
perform a reset.
7.1.5.12 D/A (Digital/Analog) Trim
Allows you to trim the 4 mA and 20 mA points in order to calibrate the mA output.
Open the menu Device-D/A Trim. You will be prompted to attach a calibrated meter and enter
the values at 4 mA and at 20 mA.
7.1.5.13 Select AnalogOut
Allows you to select one of three operation types:
level
space
distance
1. Open the menu Device – Select AnalogOut.
2. Select AnalogOut window displays the current setting: click OK.
3. Select a different setting and click OK.
4. Select AnalogOut window displays the new setting: click OK.
7.1.5.14 Simulate AO (Analog Output)
Allows you to input a simulated value in order to test the functioning of the mA connections
during commissioning or maintenance of the device.
Operating
7.1 Operating via SIMATIC PDM
SITRANS LR260 with mA/HART
70 Operating Instructions, 11/2019, A5E32337683-AD