8.3 Quick Start Wizard
The Quick Start wizard groups together all the settings you need to configure for a simple
application. You can access it either via SIMATIC PDM, or via the handheld programmer.
Note
Do not use the Quick Start wizard to modify individual parameters (perform customization for
your application only after the Quick Start has been completed).
8.4 Quick start (1.)
8.4.1 Application Type (1.1.)
Options STEEL Silo construction
CONCRETE
Default: STEEL
8.4.2 Response Rate (1.2.)
Sets the reaction speed of the device to measurement changes in the target range.
Options
SLOW 0.1 m/minute
MED 1.0 m/minute
FAST 10.0m/minute
Default: FAST
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy; faster settings allow for more level fluctuation.
Parameter reference
8.4 Quick start (1.)
SITRANS LR260 with mA/HART
74 Operating Instructions, 11/2019, A5E32337683-AD