8.5.35 Space Measurement (SPACE MEAS.) (2.2.8.3.)
The value for space. Read Only. In SIMATIC PDM, open the menu View – Display, and select
the tab Display.
8.5.36 Distance Measurement (DISTANCE MEAS.)
The value for distance. Read Only. In SIMATIC PDM, open the menu View Display, and select
the tab Display.
8.5.37 Output (2.3.)
8.5.37.1 mA Output (2.3.1.)
8.5.38 mA Output (2.3.1.)
8.5.39 mA Output Value (2.3.1.1.)
The loop current value in mA. Read Only except if the Manual option is chosen in mA Output
function below (2.3.1.2).
Values
User Entry only if Manual option is chosen in 2.3.1.2.
Range: 3.6 mA to 22.6 mA
8.5.40 mA Output Function (mA OUTPUT FUNC.) (2.3.1.2.)
Alters the mA output/measurement function and allows the output to be set independently.
Options
Manual
Level
Space
* Distance
Parameter reference
8.5 Setup (2.)
SITRANS LR260 with mA/HART
Operating Instructions, 11/2019, A5E32337683-AD 91