Operating Instructions

Table Of Contents
To request a profile via the handheld programmer:
Echo confidence value Exit icon, selected
Algorithm selection (true
first)
TVT curve
Distance value Material level
Transmit icon, deselected
1. In PROGRAM mode, navigate to LEVEL METER > DIAGNOSTICS > ECHO PROFILE
(3.1)
2. Press RIGHT arrow to request a profile.
3. In the Profile screen, press UP arrow to select the Transmit icon, and Right ARROW to
update the profile.
4. Press DOWN arrow to select the Exit icon, then Right ARROW to return to previous menu.
8.6.2 Measured Values (MEAS. VALUES) (3.14.)
8.6.3 Current Internal Temperature (CURR. INTERN. TEMP.) (3.14.1.)
Read Only. Displays (in degrees C) the current temperature on the circuit board recorded by
the internal electronics.
8.6.4 Maximum Internal Temperature (MAX. INTERN. TEMP.) (3.14.2.)
Read Only. Displays (in degrees C) the maximum temperature recorded by the internal
electronics. The high and low values are maintained over a power cycle.
8.6.5 Minimum Internal Temperature (MIN. INTERN. TEMP.) (3.14.3.)
Read Only. Displays (in degrees C) the minimum temperature recorded by the internal
electronics. The high and low values are maintained over a power cycle.
Parameter reference
8.6 Diagnostics (3.)
SITRANS LR260 with mA/HART
96 Operating Instructions, 11/2019, A5E32337683-AD