8.6.8 Remaining Device Lifetime (REMAIN. LIFETIME) (3.15.2.)
Read only. Remaining Lifetime in selected units.
8.6.9 Maintenance Required Limit (MAINT. REQ. LIMIT) (3.15.3.)
If the Remaining Lifetime is equal to or less than this limit, the device sets Maintenance
Required.
Values Range: 0 to 20 years
Default: 0.164 years
In SIMATIC PDM, open the menu Device – Maintenance, click on Remaining Device Lifetime.
1. Modify limit values as required.
2. Enable 3.15.5. Maintenance Alert Activation (ALERT ACTIVATION) .
8.6.10 Maintenance Demanded Limit (MAINT. DEM. LIMIT) (3.15.4.)
If Remaining Device Lifetime is equal to or less than this limit, a Maintenance Demanded status
is generated.
Values Range: 0 to 20 years
Default: 0.019 years
In SIMATIC PDM, open the menu Device – Maintenance, click on Remaining Device Lifetime.
1. Modify limit values as required.
2. Select the desired Maintenance Alert Activation option.
8.6.11 Maintenance Alert Activation (ALERT ACTIVATION) (3.15.5.)
Note
To modify this parameter via SIMATIC PDM it must be accessed via the pull-down
menu Device – Maintenance.
Allows you to enable a maintenance limit.
Options
Warning Limit 1 (Maintenance Required Limit)
Warning Limit 2 (Maintenance Demanded Limit)
Warning Limits 1 and 2 (Maintenance Required and Main‐
tenance Demanded Limits)
* OFF
Parameter reference
8.6 Diagnostics (3.)
SITRANS LR260 with mA/HART
98 Operating Instructions, 11/2019, A5E32337683-AD