Data Sheet for Product

Table 1. MicroFlo II Point Map, Application Number: 5713. (continued)
Point Type Description Range/Units
abc
24 LAI Duct Te mp
°F
°C
25 LAI Box Flow
cfm
Lpm
26 LAI Damper Position
%
27 LAI Percent Aux Act
%
28 LAI
Analog Output 1 %
29 LAI
Control Cool Se t point °F
°C
30 LAI
Control Heat S etpoint °F
°C
31 LAI
Control Par Fan Setpoint °F
°C
32 LAI
Control Max Flo w/Pos
33 LAI
Control Min Flow/Pos
34 LAI
Flow/Pos Setpoint
35 LAI
Remote Setpoint
36 LAI
Override Time
mins
37 LAI Velocity Pressure
IN WC
Pa
38 LDI
DO1 Status Off/On
39 LDI
DO2 Status Off/On
40 LDI
DO3 Status Off/On
41 LDI
DO4 Status Off/On
42 LDI
Digital Input Status Off/On
43 LDI
Occupancy Status Off/On
44 LAI Box Ty pe
45 LAI
Control Status
46 LAI Diagnosti c Type
a
Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
b
This column indicates the value/range or eng ineering units or both if known.
c
The default English v alue is not italicized. An italicized entry indicates an SI value.