Installation Instructions

Installation Instructions
Document No. 565-717
April 30, 2009
Barber-Colma
n Network 8000 Enhanced Driver for PXC Modular
These installation instructions cover the connection
of the Barber-Colman Network 8000 Enhanced
Driver to the Barber-Colman Barber-Colm a n System.
For hardware installation of the PXC Modular, see
document number 553-638.
Product Description
The Barber-Colman Network 8000 Enhanced Driver
enables comm u nication between the APOGEE
®
Automation System and the Barber-Colman devices.
This is done by removing the Barber-Colman GCM
and replacing it with the Barber-Colman Network
8000 Enhanced Driver, allowing the driver to control
the B arbe r-Co lman ASD bus.
LCM block functionality and LCM bus
integration are not supported with the
Barber-Colman Network 8000 Enhanced
Driver.
Product Numbers
PXC00-PE96.A PXC Modular RS-485 or Ethernet
ALN, 96 FLN nodes
PXC00-E96.A PXC Modular with BACnet/IP
ALN and BACnet MS/TP ALN, 96
FLN nodes
PXC100-PE96.A PXC Modular RS-485 or Ethernet
ALN, TX-I/O Support, 96 FLN
nodes
PXC100-E
96.A
PXC Modul
ar BACnet/IP ALN
and BACne
t MS/TP ALN, TX-I/O
Support,
96 FLN nodes
PXX-485.3
Expansion Modu le, three RS-485
FLN connection s
LSM-INT-BC8000 License for Barber-Colman
Network 8000 Enhanced PXC
Modular Driver
Warning/Caution Notations
WARNING:
Personal injury/loss of life may occur if you
do not follow the procedures as specied.
CAUTION:
Equipment d
amage or loss of data m ay
occur if you
do not follow the procedures
as specied
.
Expected I
nstallation Times
The expected installat i on time is 7 minutes.
Required Tools and Materials
Flat-blade screwdriver (1/8-inch blade width).
Wire strip
pers.
Cabling and connectors. See the Connecting
the Barber-Colman Network 8000 Enhanced
Driver to the Barber-Colman System section.
CAUTION:
Always wear an electro-static discharge
wrist strap and discharge accumulated
static before touching eld panel
components.
Prerequisites
Driver hardware is installed according to its
respective installation instructions.
•FLNTerm
ination block s installed, if any.
Depending on the type of installation, other
prerequisites may have to be completed.
I
tem N umber: 565-717, Rev. AA
P
age 1 of 2

Summary of content (2 pages)