Data Sheet for Product

Technical Specification Sheet
Document No. 588-783
May 20, 2020
1
Siemens Industry, Inc. 588-783
Smart Infrastructure 2020-05-20
TC Modular Series for BACnet Networks
Figure 1. TC Modular.
Description
The TC Modular Series for BACnet networks is a
high-performance modular Direct Digital Control
(DDC) supervisory equipment controller, which is an
integral part of the TALON Automation System. It is
classified as a BACnet Building Controller (B-BC) and
supports BACnet/IP and BACnet MS/TP protocols.
The field panel operates stand-alone or networked to
perform complex control, monitoring, and energy
management functions without relying on a higher
level processor.
Up to 100 TC Modular field panels communicate
on a peer-to-peer network.
With the addition of TX-I/O modules and a TX-I/O
Power Supply on a self-forming bus, the TC
Modular can directly control up to 500 points.
See the
TALON Wiring Guidelines Manual
(588-581) for information on setting up this
configuration.
With the addition of an Expansion Module, the TC
Modular also provides central monitoring and
control for distributed Field Level Network (FLN)
devices.
Features
BACnet Testing Laboratories (BTL) certified
Classified as BACnet Building Controllers (B-BC)
using the BACnet/IP protocol and/or BACnet
MS/TP, or BACnet Advanced Application
Controllers (B-AAC) using the BACnet MS/TP
protocol for specific models.
Modular hardware components match initial
control requirements while providing for future
expansion.
DIN rail mounted device with removable terminal
blocks simplifies installation and servicing.
Proven program sequences to match equipment
control applications.
Built-in energy management applications and
DDC programs for complete facility management.
Comprehensive alarm management, historical
data trend collection, operator control, and
monitoring functions.
HMI RS-232 and USB ports, which provide laptop
connectivity for local operation and engineering.
Extended battery backup of Real Time Clock.
Back-up battery protection eliminating the need
for time-consuming program and database re-
entry in the event of an extended power failure.
The TC Modular illuminates a “battery low” status
LED and can send an alarm message to selected
printers or terminals.
Optional support for MS/TP FLN devices.
Optional operation as a MS/TP device with
default applications.
PPCL performance during an internal database
backup has been significantly improved. PPCL
will consistently execute during the backup cycle.
Unused Ethernet ports are now disabled and do
not require the field panel to cold start.
The handling of COV subscriptions for large
databases has been improved.

Summary of content (8 pages)