Figure 1: Typical Johnson Controls N2 System Architecture on Firmware Revision 2.x. Siemens Industry, Inc.
Johnson Controls N2 Master Driver on the PXC Series Platform Functionality Notes on System Architecture The Johnson Controls N2 Master Driver with Firmware 2.x (Figure 1) supports the following: ● A maximum of 96 devices. ● Three physical FLNs (FLN 1 through FLN 3), which can be used for connecting and addressing Johnson Controls N2 Master devices on RS-485 FLNs on a PXC Modular. ● TX-I/O Modules. ● Maximum of 8,000 APOGEE points per driver.
Johnson Controls N2 Master Driver on the PXC Series Platform Functionality Notes on System Architecture The Johnson Controls N2 Master Driver with Firmware 3.x (Figure 2) supports the following: ● BACnet MS/TP or BACnet/IP ALN on Firmware 3.x. If the driver is on a BACnet MS/TP network, you can use a standard field panel with Firmware Revision 3.1 or later as a router to connect to an Insight workstation. Do not use an Integration Driver as the router. ● A maximum of 96 devices.
Johnson Controls N2 Master Driver on the PXC Series Platform Keys to Success Keys to Success Ensure that all Johnson Controls equipment to be integrated is supported by the Johnson Controls N2 Master Driver. Benefits Systems integration brings the powerful facility control capabilities of the APOGEE Automation System together with Johnson Controls system.
Johnson Controls N2 Master Driver on the PXC Series Platform Ordering Information PXC Compact Series PXC36-PE.A PXC Compact, 36 point, Ethernet/IP or RS-485 ALN. Firmware revision 3.5.1 / 2.8.18 and earlier require an additional license for P1 FLN (LSM-FLN36.A). PXC36-E.A PXC Compact, 36 point, BACnet/IP or MS/TP ALN. Firmware revision 3.5.1 / 2.8.18 and earlier require an additional license for P1 FLN (LSM-FLN36.A). PXC36-PEF.A PXC Compact, 36 point, Ethernet/IP or RS-485 ALN.