Data Sheet for Product
Table 1. VMA1200 APOGEE Points, Application Number: 9091, Program ID: 80:00:11:55:02:03:04:01. (continued)
Point Type Description Range/Units
abc
18 LENUM
Occupancy Scheduler Input Current State 0=Oc_Occupie d
1=Oc_Unoccupied
2=Oc_Bypass
3=Oc_Standby
255=Oc_Nul
19 LENUM
Occupancy Sch eduler Input Next State 0=Oc_Occupied
1=Oc_Unoccupied
2=Oc_Bypass
3=Oc_Standby
255=Oc_Nul
20
LAO Occupancy Scheduler Input Time to Next State
min
21 LENUM
Occupancy Override Input 0=Oc_Occupied
1=Oc_Unoccupied
2=Oc_Bypass
3=Oc_Standby
255=Oc_Nul
22 LENUM
Occupancy Sensor Input 0=Oc_Occupied
1=Oc_Unoccupied
2=Oc_Bypass
3=Oc_Standby
255=Oc_Nul
23 LENUM
Application Mode Comma nd See Tabl e 2
24 LENUM
Heat/Cool Mode Input See Table 2
25
LAO Fan Spe ed Command Value %
26
LAO Fan Speed Co m mand State
–
29
LAO
Auxiliary Heat Ena ble Input Value
%
30
LAO Auxiliary Heat E nable Input State
–
33
LAO Energy Hold Off Inp ut Value %
34
LAO Energy Hold Off Input State
–
35 LENUM
Water Valve Override Input State See Table 3
36
LAO Water Valve Override Input Pressure %
37
LAO Water Valve Override Input Flo w cfm
Lps
38 LENUM
Airflow Ove rride Input State See Table 3
39
LAO Airflow Override Input Pressure %
40
LAO Airflow Override Input Flow cfm
Lps
41 LENUM
Emergency Override Inpu t
0=Emerg_Normal
1=Emerg_Pressurize
2=Emerg_Depressurize
3=Emerg_Purge
4=Emerg_Shutdown
5=Emerg_Fire
255=Emerg_Nul
continued on next page...