Data Sheet for Product
Table 1. VMA1200 APOGEE Points, Application Number: 9091, Program ID: 80:00:11:55:02:03:04:01. (continued)
Point Type Description Range/Units
abc
43
LAO Outside Temperature Inp ut °F
°C
46
LAO CO2 Sensor Input
ppm
49
LAO Airflow Input cfm
Lps
50 LAI
Effective S etpoint Output °F
°C
51 LENUM
Effective Occup ancy Output 0=Oc_Occupie d
1=Oc_Unoccupied
2=Oc_Bypass
3=Oc_Standby
255=Oc_Nul
52 LENUM
Heat/Cool Output See Tabl e 2
53 LAI
Local Setpoint Output °F
°C
54 LAI
Local Setpoint Shift Output Occupied Cool °F
°C
55
LAI
Local Setpoint Shift Output Standby Cool °F
°C
56 LAI
Local Setpoint Shift Output Unoccupied Cool °F
°C
57
LAI
Local Setpoin t Shift Output Occupied Heat °F
°C
58 LAI
Local Setpoint Shift Output Standby Heat °F
°C
59 LAI
Local Setpoint Shift Output Unoccupied Heat °F
°C
60 LAI
Fan Speed Output Value %
61 LDI
Fan Speed Output State Off/On
62 LAI
Discharge Air Temperature O utpu t °F
°C
65 LAI
Terminal Load Output %
66 LAI
Primary Heat Output %
67 LAI
Secondary Heat Output %
68 LAI
Primary Cool Output %
74 LAI
Space CO 2 Sensor Output
ppm
77
LAI
Energy Hold Off Output Value %
78 LDI
Energy Hold Off Output State Off/On
79 LAI
Effective Airflow Setpoint Ou
tput
cfm
Lps
80 LAI
Flow Control Damper Setpo int Output %
continued on next page...
Siemens Building Technologies, Inc. Page 3 of 12
Document No. 127-1369