Data Sheet for Product
Siemens Building Technologies, Inc.  Page 3 of 4 
Document No. 127-0573 
Table 2. Unit Vent Mode/Fault (Point 21). 
Value Mode 
0  Unoccupied. Also, set point to this value to clear faults. 
1 Occupied 
2 Tenant Override 
3 Load Shed 
4  Tenant Load Shed 
5 Defrost 
188 Communication Error 
189 Change Filter 
190  Suction Line Temperature Sensor Bad 
191  Water In Temperature Sensor Bad 
192  Mixed Air Temperature Sensor Bad 
193  Outside Air Temperature Sensor Bad 
194  Discharge Air Temperature Sensor Bad 
195  Outside Air Damper Position Potentiometer Bad 
196  Heating Valve Position Potentiometer Bad 
197  Cooling Valve Position Potentiometer Bad 
198 Brownout 
199 Low Temperature 
200 Low Water Temperature 
201 High Pressure 
202  Room Temperature Sensor 