Data Sheet for Product
Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc.  Page 1 of 4 
Document No. 127-0576 
Systems Integration 
APOGEE
¥
 Open Processor with McQuay Microtech 
Driver: Chilled Water Cooling Only – Damper Control 
Unit Ventilator 
Table 1. Chilled Water Cooling Only – Damper Control Unit Ventilator. 
Point Type  Description  Range/Units 
01 LAO Device Address  — 
02 LAO Application Number  5036 
03  LDI  Supply Fan Status  Off/On 
04 LAI Room Temperature 
-50 – 205°F 
05  LAI  Discharge Air Temperature 
-50 – 205°F 
06  LAI  Outside Air Temperature 
-50 – 205°F 
07  LAI  Mixed Air Temperature 
-50 – 205°F 
08  LAI  Water In Temperature 
-50 – 205°F 
09  LAI  Face and Bypass Damper Position  0 – 100% 
10  LAI  Outdoor Air Damper Position  0 – 100% 
11  LAI  Outdoor Air Damper Minimum Position  0 – 100% 
12  LAI  Outdoor Air Damper Position Set Point  0 – 100% 
13  LDI  Compressor Output Status  Off/On 
14  LAI  Current (Active) Cooling Set Point 
-50 – 205°F 
15  LAI  Current (Active) Heating Set Point 
-50 – 205°F 
16  LAI  Face and Bypass Damper Position Set Point  0 – 100% 
17  LAI  Tenant Set Point Potentiometer Adjustment 
-3 – 3°F 
18  LAI  Heat/Cool Mode.  0 = Temperature is OK 
1 = Cooling 
2 = Heating 
19  LAI  Supply Fan Hours  0 – 131,070 
21  LAO  Clear Fault/Current Mode/Fault. Set point to zero to clear faults.  See Table 2 
22  LAO  Watch Dog  0 – 255 Minutes 
23 LDO Occupied Status  Unoccupied/Occupied 
continued on next page…