Data Sheet for Product
Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 8
Document No. 127-0007
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Series 200 Flooded Screw Chiller
Table 1. Series 200 Flooded Screw Chiller.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5055
03 LAI Chilled Water Temperature – Active Set Point 0 – 80°F
04 LDI Chiller Unit Temperature Type Standard/Low Temperature
05 LDI Communications Signal No Communication/
Communication OK
06 LAI Compressor Lift Pressure 0 – 6,553 psig
07 LAI Compressor Motor Current 0 – 65,535 A
08 LAI Compressor Motor Current Percent 0 – 125% RLA
09 LAI Compressor Number of Starts 0 – 49,999
10 LAI Compressor Operating Hours 0 – 49,999
11 LAI Compressor Suction Temperature -40 – 263°F
12 LAI Compressor Superheat – Discharge 0 – 263°F
13 LAI Compressor Superheat – Suction 0 – 263°F
14 LAI Condenser Approach Temperature 0 – 263°F
15 LAI Condenser Differential Pressure – Liquid Line 0 – 6,553 psi
16 LAI Condenser Pump Status See Table 2
17 LAI Condenser Pump No. 1 Operating Hours 0 – 49,999
18 LAI Condenser Pump No. 2 Operating Hours 0 – 49,999
19 LAI Condenser Refrigerant Pressure 0 – 450 psi
20 LAI Condenser Refrigerant Temperature -40 – 263°F
21 LAI Condenser Subcooling Temperature 0 – 263°F
22 LAI Condenser Water Flow Rate 0 – 6,553 GPM
23 LDI Condenser Water Flow Status No Flow/Flow
24 LDI Condenser Water Rate Sensor Not Present/Present