Data Sheet for Product
Siemens Building Technologies, Inc. Page 3 of 8
Document No. 127-0007
Table 1. Series 200 Flooded Screw Chiller.
Point Type Description Range/Units
57 LAO Chilled Water Temperature Set Point 0 – 80°F
58 LAO Watch Dog Timer 0 = No Communication
1 – 255 = Communication
59 LAO Outdoor Air Temperature – BAS -40 – 152°F
60 LAO Outdoor Air Temperature Method 0 = Not Present
1 = Local
2 = Network
61 LAI Lead/Lag Status See Table 7
62 LDI Lead Unit Master/Slave
63 LAI Lead Unit Status See Table 5
64 LAI Lag Unit Status See Table 5
65 LAI Lead Motor Current 0 – 100%
66 LAI Lag Motor Current 0 – 100%
67 LDI Lead Enabled No/Yes
68 LDI Lag Enabled No/Yes
69 LDO Master/Slave Set Point Master/Slave (Default)
70 LAO Lead/Lag Mode Set Point See Table 8
71 LAO Enable Lag Set Point 0 – 100%
(Default = 95)
72 LAO Disable Lag Set Point 0 – 100%
(Default = 40)
73 LDO Lag Standby Set Point No (Default)/Yes
74 LAO Lead/Lag Switch Set Point (Day) 1=Sunday, 7=Saturday
75 LAO Lead/Lag Switch Set Point (Hour) 0 – 23
99 LDI Communication Status Normal/Failed