Data Sheet for Product
Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 6
Document No. 127-0010
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Three-Compressor Screw Chiller
Table 1. Three-Compressor Screw Chiller.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5049
03 LAI Unit Status See Table 2
04 LAI Circuit 1 Status See Table 3
05 LAI Circuit 2 Status See Table 3
06 LAI Circuit 3 Status See Table 3
07 LAI Stage of Cooling 0 – 8
08 LAI Evaporator Leaving Water Temperature
-40 – 263°F
09 LAI Evaporator Entering Water Temperature
-40 – 263°F
10 LAI Outside Air Temperature
-40 – 263°F
11 LAI Circuit 1 Suction Temperature. Temperature of low-pressure
vaporized refrigerant entering the compressor.
-40 – 263°F
12 LAI Circuit 2 Suction Temperature. Temperature of low-pressure
vaporized refrigerant entering the compressor.
-40 – 263°F
13 LAI Circuit 3 Suction Temperature. Temperature of low-pressure
vaporized refrigerant entering the compressor.
-40 – 263°F
14 LAI Circuit 1 Liquid Line Temperature. Temperature of liquid refrigerant
entering the expansion valve.
-40 – 263°F
15 LAI Circuit 2 Liquid Line Temperature. Temperature of liquid refrigerant
entering the expansion valve.
-40 – 263°F
16 LAI Circuit 3 Liquid Line Temperature. Temperature of liquid refrigerant
entering the expansion valve.
-40 – 263°F
17 LAI Circuit 1 Superheat Temperature. Calculated by subtracting
evaporator refrigerant temp. (Point 11) from suction temperature.
0 – 263°F
18 LAI Circuit 2 Superheat Temperature. Calculated by subtracting
evaporator refrigerant temp. (Point 12) from suction temperature.
0 – 263°F
19 LAI Circuit 3 Superheat Temperature. Calculated by subtracting
evaporator refrigerant temp. (Point 13) from suction temperature.
0 – 263°F
continued on next page...