Table 5. Reset Option (Point 70).
Value Description
0 No Chilled Water Reset
1 Return Chilled Water Reset. Constant return Chilled
Water Temperature Set Point maintained.
2 4 – 20 mA Chilled Water Reset. Resets Chilled
Water Set Point based on 4 – 20 mA signal. A signal
less than 4 mA results in no reset of Chilled Water
Temperature Set Point. A signal greater than 4 mA
results in a linear reset between Chilled Water Set
Point and the maximum Chilled Water Reset Set
Point plus the Chilled Water Set Point.
3 Network Chilled Water Reset. Resets Chilled Water
Set Point based on the network evaporator leaving
temperature reset. A signal of 0 – 100% results in a
linear reset between the Chilled Water Set Point and
the Maximum Chilled Water Reset Set Point plus the
Chilled Water Set Point.
4 Ice Chilled Water Reset. Resets the Chilled Water
Set Point (typically 23°F) based upon a 4 – 20 mA
signal. A signal less than 4 mA results in no reset of
Chilled Water Temperature Set Point. A signal
greater than 4 mA results in a Chilled Water Set
Point equal to the set point plus the Maximum
Chilled Water Reset Set Point (typically 22°F).
5 Outdoor Air Temperature Chilled Water Reset.