Data Sheet for Product
Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc.  Page 1 of 8 
Document No. 127-0550 
Systems Integration 
APOGEE
¥
 Open Processor with McQuay Microtech 
Driver: Constant Volume, Outside Air, Zone Control 
Rooftop Unit 
Table 1. Constant Volume, Outside Air, Zone Control Rooftop Unit. 
Point Type  Description  Range/Units 
01  LAO  Device Address  — 
02 LAO Application Number  5016 
03  LAI  Supply Air Temperature 
1 – 255°F 
05  LAI  Outdoor Air Temperature 
-40 – 150°F 
06 LAI Space Temperature 
1 – 240°F 
08  LAI  Misc. Temperature 1 (Optional) 
1 – 240°F 
09  LAI  Misc. Temperature 2 (Optional) 
1 – 240°F 
10  LAI  Final Filter Pressure Drop (Optional)  0 – 4 IWC 
11  LAI  Filter Pressure Drop  0 – 4 IWC 
15  LAI  Humidity  0 – 100% rh 
17  LAI  Control Temperature  See Table 2 
18  LAI  Unit Status  See Table 3 
19  LAI  Stages of Cooling/Heating. Zero indicates no Heating or Cooling.  — 
21  LAI  Cooling Control Status  See Table 4 
22  LAI  Heating Control Status  See Table 5 
23  LAI  Time Mode Status  Occupied/Unoccupied 
25  LDI  Airflow Status  No Airflow/Airflow 
26  LDI  Supply Fan Status  Off/On 
28  LAI  Reheat Operating Hours  Hours 
29 LAI Dewpoint Temperature 
°F 
30  LAI  Current Alarm (Buffer)  See Table 6 
31 LAI Cooling Stages  Number 
32 LAI Heating Stages  Number 