Table 1. Constant Volume, Outside Air, Zone Control Rooftop Unit. 
Point Type  Description  Range/Units 
33 LAI Reheat Stages  Number 
34  LAI  Reheat Set Point 
°F 
37  LDO  Outside Air Source Type  Local/Remote 
38 LAO Reheat Deadband 
0 – 10°F 
39  LDO  Humidity Control Type  Humidity/Dewpoint 
40  LAO  Humidity Set Point  0 – 100% 
41  LAO  Humidity Deadband  0 – 10% 
42  LAO  Dewpoint Set Point 
0 – 87°F 
43 LAO Dewpoint Deadband 
0 – 10°F 
44  LAO  Minimum Dehumidification Cool Stage  0 – 8 
45  LDO  Clear Alarm. Warning and problem conditions are normally self-
clearing once abnormal condition is resolved. Fault conditions cause 
unit to shut down and must be manually cleared. Refer to alarms 
later in this section for more information. 
Point automatically reset to 0 after 
alarm is cleared/Clears active fault. 
46  LAO  Control Mode  See Table 7 
47  LAO  Override Timer. The unit does not start if a shut down fault is active 
or the unit is manually disabled through the keypad, monitor 
program, or remote panel. Set to zero for unoccupied mode. ≤ 1 sets 
point to occupied mode if manual mode set to auto. 
0 – 300 Minutes 
48  LAO  Control Temperature Sensor  See Table 2 
49  LDO  Set Point Source. Constant volume units can use space temperature 
set points from a room thermostat or set points in software. 
Thermostat/Point 50, Point 53 
50  LAO  Heating Space Set Point. If set point source point is 1, this point is 
active heating set point. If it is 0, thermostat determines the set point. 
Night setback (NSB) is active during unoccupied time period. 
40 – 99°F 
52  LAO  Heating Space Deadband 
0 – 10°F 
53  LAO  Cooling Space Set Point. If set point source point is 1, this point is 
the active cooling set point. If it is 0, the thermostat determines set 
point. The night setup (NSU) set point is active during the 
unoccupied time period. 
55 – 99°F 
54  LAO  Cooling Space Differential 
1 – 10°F 
55  LAO  Cooling Space Deadband 
0 – 10°F 
56  LAO  Night Setback Space Set Point 
40 – 99°F 
57  LAO  Night Setback Space Differential 
1 – 10°F 
58  LAO  Night Setup Space Set Point 
55 – 99°F 
59  LAO  Night Setup Space Differential 
1 – 10°F 
60  LAO  Cooling Supply Set Point. Control temperature for supply air when 
unit is in an active cooling state. Point is adjustable only when no 
reset is selected. 
40 – 100°F 
continued on next page…