Data Sheet for Product
Siemens Building Technologies, Inc.  Page 3 of 8 
Document No. 127-0550 
Table 1. Constant Volume, Outside Air, Zone Control Rooftop Unit. 
Point Type  Description  Range/Units 
61  LAO  Cooling Supply Deadband 
0 – 10°F 
62  LAO  Cooling Reset Type  See Table 8 
63  LAO  Minimum Cooling Supply Set Point 
40 – 100°F 
64  LAO  Maximum Cooling Supply Set Point 
40 – 100°F 
65  LAO  Minimum Cooling Supply Set Point @ 
0 – 100°F 
66  LAO  Maximum Cooling Supply Set Point @ 
0 – 100°F 
67  LAO  Heating Supply Set Point. Control temperature for supply air when 
unit is in an active heating state. Point is adjustable only when no 
reset is selected. 
40 – 140°F 
68  LAO  Heating Supply Deadband 
0 – 10°F 
69  LAO  Heating Reset Type  See Table 9 
70  LAO  Minimum Heating Supply Set Point 
40 – 140°F 
71  LAO  Maximum Heating Supply Set Point 
40 – 140°F 
72  LAO  Minimum Heating Supply Set Point @ 
0 – 100°F 
73  LAO  Maximum Heating Supply Set Point @ 
0 – 100°F 
74  LAO  Network Supply Air Reset 
0 – 20°F 
75  LAO  Duct Static Pressure Set Point  0.20 – 4 IWC 
76  LAO  Duct Static Pressure Deadband  0 – 0.5 IWC 
81  LAO  Maximum Dehumidification Cool Stage  0 – 8 
86  LAO  Final Filter Pressure Set Point. This point controls when filters are 
considered dirty. If pressure difference across either filter is greater 
than or equal to set point, dirty filter warning is activated. 
0 – 5.1 IWC 
87  LAO  Filter Pressure Set Point. This point controls when the filters are 
considered dirty. If pressure difference across either filter is greater 
than or equal to set point, dirty filter warning is activated. 
0 – 5.1 IWC 
88  LAO  High Supply Temperature Limit 
90 – 250°F 
89  LAO  Low Supply Temperature Limit 
20 – 50°F 
91  LAO  Network Control Temperature. Uses the network supplied control 
temp. (See Points 17 and 48). 
40 – 100°F 
92  LAO  Network Supply Vane Position. Supply vane position controlled to 
maintain this point. 
0 – 100% 
93  LAO  Network Watch Dog  1 – 255 
94  LAI  Fan Operating Hours  — 
95  LAI  Cooling Operating Hours  — 
96  LAI  Heating Operating Hours  — 
97  LAI  Override Operating Hours  — 
98  LAO  Network Outside Air Temperature 
-100 – 155°F 
99  LDI  Device Communication Failure  Normal/Failed 