Data Sheet for Product
Siemens Building Technologies, Inc.  Page 5 of 8 
Document No. 127-0550 
Table 3. Unit Status (Point 18). 
Value Description 
25 Unoccupied Economizer 
26 Unoccupied Cooling 
27  Unoccupied Cooling Stage XX Minutes 
28 Dehumidify 
Table 4. Cooling Control Status (Point 21). 
Value Description 
0  Off – Temperature/Enthalpy Disabled 
1  Off – Enable Switch 
2  Off – Schedule 
3  Off – Bridge 
4  Off – Network 
5  Off – Manual 
6  Off – Fault 
7 No Economizer 
8  Economizer Disabled, High Enthalpy 
9  Compressors Disabled, Low Temperature 
10  Cool Enabled 
Table 5. Heating Control Status (Point 22). 
Value Description 
0  Off – Enable Switch 
1  Off – Bridge 
2  Off – Network 
3  Off – Manual 
4  Off – Fault 
5 Heat Enabled 
6  Off – High Temperature 
7  Off – Schedule 