Table 6. Alarms (Point 30). 
Point Type  Description 
0 — No Alarm 
1  Warning  Miscellaneous Temperature Sensor 1 Shorted or Open 
2  Warning  Miscellaneous Sensor 2 Shorted or Open 
3  Warning  Final Filter Dirty. Pressure drop above limit. 
4  Warning  Standard Filter Dirty. Pressure drop above limit. 
5  Warning  Airflow Warning. Unit is off and digital input indicates airflow. 
6  Warning  Outside Air Damper Stuck. Damper is open when the unit is off, 
or damper is not completely open when it should be. 
7  Problem  Cooling Circuit 1 Failure. Compressor Cooling Units Only. 
Results from Compressor Shutdown by Safety Device. 
8  Problem  Cooling Circuit 2 Failure. Compressor Cooling Units Only. 
Results from Compressor Shutdown by Safety Device. 
9  Problem  Cooling Circuit 3 Failure. Compressor Cooling Units Only. 
Results from Compressor Shutdown by Safety Device. 
10  Problem  Heat Fail. Only for units with gas heat. 
11  Problem  Low Airflow. Temperature rise across heater is too high. Heat 
Disabled. VAV Units Only. 
12  Problem  Mixed Air Temperature Sensor Shorted or Open. 
13  Problem  Supply Air Temperature Sensor Shorted or Open. 
14  Problem  Return Air Temperature Sensor Shorted or Open. 
15 Problem Space Temperature Sensor Shorted or Open. 
16  Problem  Outdoor Air Temperature Sensor Shorted or Open. 
17  Problem  Freeze Problem. Digital Freeze Input closes after unit is turned 
off. 
18  Fault  Supply Vanes Open when Unit attempts to start. VAV Units 
Only. 
19  Fault  Fan Fail. Airflow Switches Open after unit is on. 
20  Fault  Supply Temperature Below Low Limit after Unit is On. 
21  Fault  Supply Temperature Above High Limit after Unit is On. 
22  Fault  Return Temperature Above High Limit after Unit is On. 
23  Fault  Duct High Limit Switch Open. VAV Units Only. 
24  Fault  Supply Air Temperature Sensor Shorted or Open. 
25  Fault  Return Air Temperature Sensor Shorted or Open and is 
selected as the Control Temperature. 
26  Fault  Space Temperature Sensor Shorted or Open and is selected 
as the Control Temperature. 