Data Sheet for Product
Siemens Building Technologies, Inc.  Page 7 of 8 
Document No. 127-0550 
Table 6. Alarms (Point 30). 
Point Type  Description 
27  Fault  Outside Air Temperature Sensor Shorted or Open and is 
selected as the Control Temperature. VAV with modulating 
Heat only. 
28  Fault  Smoke Detector Input Open 
29  Fault  Freeze Shutdown. Digital Freeze Input Closes while Unit is 
Operating. 
Table 7. Control Mode (Point 46). 
Value Description 
0  Off – No Unoccupied Operation 
1 Auto 
2  On – Cool and Heat Enabled 
3  On – Cool Enabled, Heat Disabled 
4  On – Cool Disabled, Heat Enabled 
5  On – Cool and Heat Disabled 
Table 8. Cooling Reset (Point 62). 
Value Description 
0 No Reset 
1  Based on Space Temperature or Control 
Temperature 
2  Based on Return Temperature 
3  Based on Outdoor Temperature 
4  Based on Network Supplied Temperature 
5  Based on External Signal 
6  Based on Airflow or Humidity (VAV Only) 
7  Based on Humidity (VAV Only) 