Data Sheet for Product

Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 8
Document No. 127-0023
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: European Reciprocating Chiller (CR2)
Table 1. European Reciprocating Chiller (CR2).
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5007
03 LAI Unit Status See Table 2
04 LAI Circuit 1 Status See Table 3
05 LAI Circuit 2 Status See Table 3
06 LAI Stage Of Cooling. Normal mode for chiller while cooling. Point
displays number of currently active cooling stages which only
indicate system capacity and not which compressors or circuits are
on.
1 – 8
07 LAI Leaving Evaporator Water Temperature
-40 – 263°F
08 LAI Entering Evaporator Water Temperature
-40 – 263°F
09 LAI Leaving Condenser Water Temperature
-40 – 263°F
10 LAI Entering Condenser Water Temperature or Outside Air Temperature
-40 – 263°F
11 LAI Circuit 1 Suction Temperature
-40 – 263°F
12 LAI Circuit 2 Suction Temperature
-40 – 263°F
13 LAI Circuit 1 Liquid Line Temperature
-40 – 263°F
14 LAI Circuit 2 Liquid Line Temperature
-40 – 263°F
15 LAI Circuit 1 Superheat. Suction temperature minus evaporator
temperature.
°F
16 LAI Circuit 2 Superheat. Suction temperature minus evaporator
temperature.
°F
17 LAI Circuit 1 Condenser Approach Temperature. Condenser refrigerant
temperature minus leaving condenser refrigerant temperature.
°F
18 LAI Circuit 2 Condenser Approach Temperature. Condenser refrigerant
temperature minus leaving condenser refrigerant temperature.
°F
19 LAI Circuit 1 Subcooling. Leaving condenser water temperature minus
liquid line temperature.
°F
continued on next page...