Open Processor with McQuay Microtech
Driver: Global Scroll Chiller
Table 1. Global Scroll Chiller.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5057
03 LAI Circuit No. 1 Condenser Pressure 0 – 450 psi
04 LAI Circuit No. 1 Conditions at Time of Alarm: Condenser Pressure 0 – 450 psi
05 LAI Circuit No. 1 Conditions at Time of Alarm: Evaporator Pressure 0 – 145 psi
06 LAI Circuit No. 1 Conditions at Time of Alarm: Liquid Line Temperature -40 – 263°F
07 LAI Circuit No. 1 Conditions at Time of Alarm: Suction Temperature -40 – 263°F
08 LAI Circuit No. 1 Current Alarm See Table 2
09 LAI Circuit No. 1 Evaporator Pressure 0 – 145 psi
10 LAI Circuit No. 1 Liquid Line Temperature -40 – 263°F
11 LAI Circuit No. 1 Previous Alarm See Table 2
12 LAI Circuit No. 1 Status See Table 3
13 LAI Circuit No. 1 Subcooling Temperature 0 – 263°F
14 LAI Circuit No. 1 Suction Temperature -40 – 263°F
15 LAI Circuit No. 1 Superheat Temperature 0 – 263°F
16 LAI Circuit No. 2 Condenser Pressure 0 – 450 psi
17 LAI Circuit No. 2 Conditions at Time of Alarm: Condenser Pressure 0 – 450 psi
18 LAI Circuit No. 2 Conditions at Time of Alarm: Evaporator Pressure 0 – 145 psi
19 LAI Circuit No. 2 Conditions at Time of Alarm: Liquid Line Temperature -40 – 263°F
20 LAI Circuit No. 2 Conditions at Time of Alarm: Suction Temperature -40 – 263°F
21 LAI Circuit No. 2 Current Alarm See Table 2
22 LAI Circuit No. 2 Evaporator Pressure 0 – 145 psi
23 LAI Circuit No. 2 Liquid Line Temperature -40 – 263°F
24 LAI Circuit No. 2 Previous Alarm See Table 2
25 LAI Circuit No. 2 Status See Table 3