Table 5. Reset Option (Point 51).
Value Description
0 No Chilled Water Reset
1 Return Chilled Water Reset. Constant return Chilled Water
Temperature Set Point maintained.
2 4 – 20 mA Chilled Water Reset. Resets Chilled Water Set
Point based on 4 – 20 mA signal. A signal less than 4 mA
results in no reset of Chilled Water Temperature Set Point.
A signal greater than 4 mA results in a linear reset between
Chilled Water Set Point and the Maximum Chilled Water
Reset Set Point plus the Chilled Water Set Point.
3 Network Chilled Water Reset. Resets Chilled Water Set
Point based on the Network Evaporator Leaving
Temperature Reset. A signal of 0 – 100% results in a linear
reset between the Chilled Water Set Point and the
Maximum Chilled Water Reset Set Point plus the Chilled
Water Set Point.
4 Ice Chilled Water Reset. Resets the Chilled Water Set Point
(typically 23°F) based upon a 4 – 20 mA signal. A signal
less than 4 mA results in no reset of Chilled Water
Temperature Set Point. A signal greater than 4 mA results
in a Chilled Water Set Point equal to the set point plus the
Maximum Chilled Water Reset Set Point (typically 22°F).