Data Sheet for Product
Siemens Building Technologies, Inc. Page 5 of 6
Document No. 127-0022
Table 3. Circuit Status (Points 13 and 27).
Value Description for Circuit 1 Status Description for Circuit 2 Status
0 Off – S-1 System Switch Off – S-1 System Switch
1 Off – Manual Set Point Off – Manual Set Point
2 Off – Alarm Off – Alarm
3 Off – Pump-down Switch Off – Pump-down Switch
4 Off – Wait for Cycle Off – Wait for Cycle
5 Off – Ready to Start Off – Ready to Start
6 Start Pump-down Start Pump-down
7 Pump-down Pump-down
8 Wait for Cooling Pressure Wait for Cooling Pressure
9 Cooling Cooling
Table 4. Unit Status (Point 46).
Value Description
0 Off – Manual Set Point
1 Off – S-1 Switch
2 Off – Remote Communication
3 Off – Remote Switch
4 Off – Time Schedule
5 Off – Alarm
6 Off – Pump-down Switches
7 Off – Ready to Start
8 Starting
9 Waiting for Flow
10 Waiting for Load
11 Cooling Stage-up
12 Cooling Stage-down
13 Cooling Staging
14 Manual Cooling Staging