Data Sheet for Product

Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc. Page 1 of 8
Document No. 127-0546
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: VAV, Modulating Heat, Fan Tracking Rooftop
Unit
Table 1. VAV, Modulating Heat, Fan Tracking Rooftop Unit.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5012
03 LAI Supply Air Temperature
1 – 255°F
04 LAI Return Air Temperature
1 – 240°F
05 LAI Outdoor Air Temperature
-40 – 150°F
06 LAI Space Temperature
1 – 240°F
07 LAI Mixed Air Temperature
1 – 240°F
08 LAI Misc. Temperature 1 (Optional)
1 – 240°F
09 LAI Misc. Temperature 2 (Optional)
1 – 240°F
10 LAI Final Filter Pressure Drop (Optional) 0 – 4 IWC
11 LAI Filter Pressure Drop 0 – 4 IWC
12 LAI Supply Fan Vane Position 0 – 100%
13 LAI Return Fan Vane Position 0 – 100%
14 LAI Outdoor Air Damper Position 0 – 100%
15 LAI Static Pressure 1 0 – 5.1 IWC
16 LAI Static Pressure 2 0 – 5.1 IWC
17 LAI Control Temperature See Table 2
18 LAI Unit Status See Table 3
19 LAI Stages of Cooling/Heating. Zero indicates no heating or cooling.
20 LDI Enthalpy Low Enthalpy/High Enthalpy
21 LAI Cooling Control Status See Table 4
22 LAI Heating Control Status See Table 5
23 LAI Time Mode Status Occupied/Unoccupied
24 LDI VAV Output Heat/Cool
continued on next page...