Data Sheet for Product
Page 4 of 8 Siemens Building Technologies, Inc.
Document No. 127-0546
Table 1. VAV, Modulating Heat, Fan Tracking Rooftop Unit.
Point Type Description Range/Units
96 LAI Heating Operating Hours —
97 LAI Override Operating Hours —
98 LAO Network Outside Air Temperature
-100 – 155°F
99 LDI Device Communication Failure Normal/Failed
Table 2. Control Temperature (Point 17 and 48).
Value Description
0 Return Temperature
1 Space Temperature
2 Network
3 Outside Air Temperature
4 None
Table 3. Unit Status (Point 18).
Value Description
0 Program Inactive
1 Off – Fan Switch
2 Off – Unoccupied
3 Off – Network
4 Off – Manual
5 Off – Service
6 Off – Alarm
7 Calibrate
8 Start Requested
9 Startup Initialize
10 Recirculation
11 Fan On
12 Balance
13 Unoccupied Heating
14 Unoccupied Heating Stage XX Minutes
15 Morning Warmup
16 Morning Warmup Stage XX Minutes