Data Sheet for Product

Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 8
Document No. 127-0014
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Self-Contained Air Conditioner
Table 1. Self-Contained Air Conditioner.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5043
03 LAI Air Velocity -419 – 1675 FPM
04 LDI Airflow No Flow/Flow
05 LAI Building Static Pressure 0 – 0.51 IWC
06 LAI Compressor No. 1 Alarm See Table 2
07 LAI Compressor No. 1 Operating Hours Hours
08 LAI Compressor No. 2 Alarm See Table 2
09 LAI Compressor No. 2 Operating Hours Hours
10 LAI Compressor No. 3 Alarm See Table 2
11 LAI Compressor No. 3 Operating Hours Hours
12 LAI Compressor No. 4 Alarm See Table 2
13 LAI Compressor No. 4 Operating Hours Hours
14 LAI Compressor No. 5 Alarm See Table 2
15 LAI Compressor No. 5 Operating Hours Hours
16 LAI Compressor No. 6 Alarm See Table 2
17 LAI Compressor No. 6 Operating Hours Hours
18 LAI Control Temperature
0 – 255°F
19 LAI Cool Stage 0 – 8
20 LAI Cooling Control Status See Table 3
21 LAI Current Fault See Table 4
22 LAI Dewpoint Temperature
0 – 70°F
23 LAI Duct Static Pressure No. 1 0 – 5.1 IWC
24 LAI Duct Static Pressure No. 2 0 – 5.1 IWC
25 LDI Economizer Enable Enabled/Disabled
continued on next page...