Data Sheet for Product

Siemens Building Technologies, Inc. Page 7 of 8
Document No. 127-0014
Table 9. Self-Contained Air Conditioner (Output Points).
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5060
03 LAO Building Static Pressure Set Point -0.25 – 0.25 IWC
04 LDO Clear Alarm No/Yes
05 LAO Control Mode See Table 10
06 LAO Control Temperature Source 0 = Return, 2 = Network
07 LAO Cooling Space Deadband
1 – 10°F
08 LAO Cooling Space Set Point
40 – 100°F
09 LAO Cooling Control Deadband
1 – 10°F
10 LAO Cooling Supply Set Point
40 – 100°F
11 LAO Dewpoint Deadband
1 – 10°F
12 LDO Dewpoint Sensor Type Return/Space
13 LAO Dewpoint Set Point
0 – 99°F
14 LAO Duct Static Pressure Set Point 0.02 – 0.4 IWC
15 LAO Duct Static/Building Static Pressure Deadband 0 – 0.1 IWC
16 LAO Economizer Changeover Temperature Differential
1 – 10°F
17 LAO Economizer Changeover Temperature Set Point
0 – 100°F
18 LDO Economizer Method Dry Bulb/Enthalpy
19 LAO Ecomizer Changeover Temperature Offset
0 – 10°F
20 LAO Fan On Heating Set Point
40 – 140°F
21 LAO Head Pressure Deadband 0 – 10 psi
22 LAO Head Pressure Set Point 0 – 255 psi
23 LAO Heating Control Deadband
1 – 10°F
24 LAO Heating Control Set Point
40 – 99°F
25 LAO Heating Supply Deadband
0 – 10°F
26 LAO Heating Supply Set Point
40 – 140°F
27 LAO Humidity Control Type 0 = None
1 = Relative Humidity Control
2 = Dewpoint Control
28 LAO Humidity Deadband 0 – 10% rh
29 LAO Humidity Set Point 0 – 99% rh
30 LAO Low Entering Water Compressor Lockout Differential
0 – 10°F
31 LAO Low Entering Water Compressor Lockout Set Point
0 – 100°F
32 LAO Minimum Vane Position For Building Static Press Control 0 – 100%
33 LAO Minimum Outdoor Air Damper Position 0 – 100%
continued on next page...