Table 9. Self-Contained Air Conditioner (Output Points).
Point Type Description Range/Units
34 LDO Minimum Supply Air Temperature Control No/Yes
35 LAO Unoccupied Cooling Space Differential
1 – 10°F
36 LAO Unoccupied Cooling Space Set Point
55 – 99°F
37 LAO Unoccupied Heating Space Differential
1 – 10°F
38 LAO Unoccupied Heating Space Set Point
40 – 99°F
39 LDO Waterflow
40 LAO Network Control Temperature
0 – 255°F
41 LAO Network Signal (Watchdog Timer)
0 – 255°F
42 LAO Network Supply Vane Position/Speed Set Point 1 – 100%
99 LDI Device Communication Failure Normal/Failed
Table 10. Control Mode (Point 5).
Value Description
0 Off – No Unoccupied Operation
1 Auto – Unoccupied
2 On – Cooling and Heating Enabled
3 On – Cooling Enabled, Heating Disabled
4 On – Cooling Disabled, Heating Enabled
5 On – Cooling and Heating Disabled