Data Sheet for Product

FLN Solution for Baldor Product Update
Development Status
FLN Solution for Baldor Product Update
Development Status
The Baldor VS1PF FLN (P1) interface is complete and available now.
Platform Type
FLN port on a PXC Modular.
Vendor Description
For more information, see www.baldor.com.
Vendor Issues
Configuration
The VS1PF connects to the FLN using an external FLN communication interface
purchased from Baldor.
Other models of Baldor VFDs do not have an FLN interface. However, there may be
other options, such as Modbus, that may be feasible. Please consult the Integration
Solutions team for specific information.
Functionality
The Baldor P1 interface allows data from the VS1PF communicating with P1 to be
mapped into APOGEE® points. All programming and standard system functions
(PPCL, enhanced alarming, trending and point definition) remain intact. The points
from the VFD appear as native APOGEE points. Auto unbundling of points helps build
the database quickly.
Estimating and Ordering
Estimating
At this time, no pricing agreement has been reached with Baldor for the purchase of
the VFD. Contact the local Baldor distributor for price and availability.
Ordering
All orders are placed through Baldor distributors.