Data Sheet for Product
Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc. Page 1 of 4
Document No. 127-0552
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Steam Powered, Cooling Only (NC-U) Absorption
Chiller
Table 1. Steam Powered, Cooling Only (NC-U) Absorption Chiller.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5050
03 LAI Unit Model Number See Table 2
04 LAI Communication Error 0 = Error
1 – 255 = No Error
05 LAI Chilled Water Temperature Set Point
°F
06 LAI Chilled Water Inlet Temperature °F
07 LAI Chilled Water Outlet Temperature °F
08 LAI Condensed Refrigerant Temperature °F
09 LAI Cooling Water Inlet Temperature °F
10 LAI Cooling Water Outlet Temperature °F
11 LAI Steam Condensate Temperature °F
14 LAI High Temperature Generator Temperature °F
15 LAI Low Temperature Generator Temperature °F
16 LAI Hot Water Temperature Set Point °F
21 LAI Inverter Output Signal Hz
22 LAI Remote Reset Current Signal mA
23 LAI Steam Control Valve Output Signal 0 – 100%
25 LAI Unit Starts —
26 LAI Unit Starts —
27 – 28 LAI Absorbent Pump 1 Starts —
31 – 32 LAI Refrigerant Pump Starts —
33 - 34 LAI Unit Operating Hours —
35 – 36 LAI Absorbent Pump 1 Operating Hours —