Data Sheet for Product

Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc. Page 1 of 4
Document No. 127-0568
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: DX Cooling with Steam or Hot Water Heat and
Damper Control Unit Ventilator
Table 1. DX Cooling with Steam or Hot Water Heat and Damper Control Unit Ventilator.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5028
03 LDI Supply Fan Status Off/On
04 LAI Room Temperature
-50 – 205°F
05 LAI Discharge Air Temperature
-50 – 205°F
06 LAI Outside Air Temperature
-50 – 205°F
07 LAI Mixed Air Temperature
-50 – 205°F
08 LAI Water In Temperature
-50 – 205°F
09 LAI Face and Bypass Damper Position 0 – 100%
10 LAI Outdoor Air Damper Position 0 – 100%
11 LAI Outdoor Air Damper Minimum Position 0 – 100%
12 LAI Outdoor Air Damper Position Set Point 0 – 100%
13 LDI Compressor Output Status Off/On
14 LAI Current (Active) Cooling Set Point
-50 – 205°F
15 LAI Current (Active) Heating Set Point
-50 – 205°F
16 LAI Face and Bypass Damper Position Set Point 0 – 100%
17 LAI Tenant Set Point Potentiometer Adjustment
-3 – 3°F
18 LAI Heat/Cool Mode. 0 = Temperature is OK
1 = Cooling
2 = Heating
19 LAI Supply Fan Hours 0 – 131,070
20 LAI Number of Compressor Starts 0 – 655,350
21 LAO Clear Fault/Current Mode/Fault. Set point to zero to clear faults. See Table 2
22 LAO Watch Dog 0 – 255 Minutes
continued on next page...