Data Sheet for Product

Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 2
Document No. 127-0026
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Lead-Lag-Load Balance
Table 1. Lead-Lag-Load Balance.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5005
03 LAO Mode See Table 2
04 LAO Chilled Water Reset. Compressors are controlled using the leaving
evaporator set point. Both compressors must have the same set
point.
0 – 100%
05 LAO Demand Reset. This reset limits the amp usage for all chillers on the
network. Both compressors must have the same set point. The
demand reset ranges from no demand to the maximum demand limit
set point.
0 – 100%
06 LDI Chiller 1 Communication Status Error/OK
07 LDI Chiller 2 Communication Status Error/OK
08 LDI Chiller 2 In Lead Chiller 1 Lead
Chiller 2 Lag/Chiller 1 Lag
Chiller 2 Lead
09 LAI Enable Lag Run Load Amps (RLA) 80 – 100%
10 LAI Disable Lag Run Load Amps (RLA) 35 – 60%
11 LAI Delay Time Control 1 – 10 minutes
99 LDI Device Communication Failure Normal/Failed