Data Sheet for Product
Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 4
Document No. 127-0018
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Large Water Source Heat Pump
Table 1. Large Water Source Heat Pump.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5041
03 LAI Space Temperature
°F
04 LAI Discharge Air Temperature
°F
05 LAI Leaving Water Temperature
°F
06 LAI Operating Mode See Table 2
07 LAI Set Point Adjustment
-3 – 3°F
08 LAI Heating Set Point
°F
09 LAI Cooling Set Point
°F
10 LDI Room Too Warm Off/On
11 LDI Room Too Cool Off/On
12 LDI Change Filter Off/On
13 LDI Rapid Cycling Off/On
14 LDI Bad Discharge Air Temperature Sensor Off/On
15 LDI Bad Leaving Water Temperature Sensor Off/On
16 LDI Request Loop Flow Off/On
17 LAI Current Fault SeeTable 3
18 LAI Previous Fault See Table 3
19 LAI Compressor 1 Fault See Table 3
20 LAI Compressor 2 Fault See Table 3
21 LDI Fan Off/On
22 LAI Fan Run Hours Rolls over at 50,000
23 LDI Compressor 1 Off/On
24 LAI Compressor 1 Run Hours Number of Hours
25 LAI Compressor 1 Starts Rolls over at 655,360
continued on next page...