Data Sheet for Product
Point Map
September 8, 2004
Systems Integration
APOGEE
®
Open Processor with McQuay Microtech
Driver: Two-Compressor Screw Chiller
Table 1. Two-Compressor Screw Chiller.
Point Type Description
Range/Units
1
LAO
Device Address
—
2
LAO
Application Number 5048
3LAI
Unit Status See Table 2
4LAI
Circuit 1 Status SeeTable 3
5
LAI
Circuit 2 Status See Table 3
6LAI
Stage of Cooling
0–8
7
LAI Evaporator Leaving Water
Temperature
-40–263°F
8 LAI Evaporat
or Entering Water
Temperat
ure
-40–263°F
9LAI
Condenser Leaving Water
Temperature
-40–263°F
10 LAI
Condenser Entering Water
Temperature
-40–263°F
11 LAI
Outside Air Temperature -40 – 263°F
12 LAI
Circuit 1 Suction
Temperature. Temperature
of low-pressure va porized
refrigerant entering the
compressor.
-40–263°F
13 LAI
Circuit 2 Suction
Temperature. Temperature
of low-pressure va porized
refrigerant entering the
compressor.
-40–263°F
14 LAI
Circui
t 1 Liquid Line
Temp e r
ature. Temperature
of liqu
id refrigerant entering
the exp
ansion valve.
-40–26
3°F
continued on next page...
S
iemens Building Technologies, Inc.
P
age 1 of 8
D
ocument No. 127-0011