Data Sheet for Product
Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc. Page 1 of 4
Document No. 127-0553
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Direct Fired, Cooling Only (DC-U) Absorption
Chiller
Table 1. Direct Fired, Cooling Only (DC-U) Absorption Chiller.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5051
03 LAI Unit Model Number See Table 2
04 LAI Communication Error 0 = Error
1–255 = No Error
05 LAI Chilled Water Temperature Set Point
°F
06 LAI Chilled Water Inlet Temperature °F
07 LAI Chilled Water Outlet Temperature °F
08 LAI Condensed Refrigerant Temperature °F
09 LAI Cooling Water Inlet Temperature °F
10 LAI Cooling Water Outlet Temperature °F
11 LAI Exhaust Gas Temperature °F
12 LAI Fuel Control Valve 1 0 – 100%
14 LAI High Temperature Generator Temperature °F
15 LAI Low Temperature Generator Temperature °F
16 LAI Hot Water Temperature Set Point °F
19 LAI Hot Water Outlet Temperature °F
21 LAI Inverter Output Signal Hz
22 LAI Remote Reset Current Signal mA
25 – 26 LAI Unit Starts
—
27 – 28 LAI Absorbent Pump 1 Starts
—
29 – 30 LAI Burner Starts
—
31 – 32 LAI Refrigerant Pump Starts
—
continued on next page...