Data Sheet for Product

Point Map
Rev. 1, February, 2002
Siemens Building Technologies, Inc. Page 1 of 4
Document No. 127-0555
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Direct Fired, Heating and Cooling (DC-S)
Absorption Chiller
Table 1. Direct Fired, Heating and Cooling (DC-S) Absorption Chiller.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5053
03 LAI Unit Model Number See Table 2
04 LAI Communication Error 0 = Error
1–255 = No Error
05 LAI Chilled Water Temperature Set Point
°F
06 LAI Chilled Water Inlet Temperature °F
07 LAI Chilled Water Outlet Temperature °F
08 LAI Condensed Refrigerant Temperature °F
09 LAI Cooling Water Inlet Temperature °F
10 LAI Cooling Water Outlet Temperature °F
11 LAI Exhaust Gas Temperature °F
14 LAI High Temperature Generator Temperature °F
15 LAI Low Temperature Generator Temperature °F
16 LAI Hot Water Temperature Set Point °F
18 LAI Hot Water Inlet Temperature °F
20 LAI Hot Water Outlet Temperature °F
21 LAI Inverter Output Signal Hz
22 LAI Remote Reset Current Signal mA
25 – 26 LAI Unit Starts
27 – 28 LAI Absorbent Pump 1 Starts
29 – 30 LAI Burner Starts
31 – 32 LAI Refrigerant Pump Starts
33 – 34 LAI Unit Operating Hours ——
continued on next page...

Summary of content (4 pages)