Data Sheet for Product
Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 6
Document No. 127-0015
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Loop Water Controller
Table 1. Loop Water Controller.
Point Type Description Range/Units
01 LAO Device Address —
02 LAO Application Number 5042
03 LAI Loop Water Supply Temperature
°F
04 LAI Loop Water Return Temperature
°F
05 LAI Entering Tower Temperature
°F
06 LAI Leaving Tower Temperature
°F
07 LAI Outside Air Temperature
°F
08 LAI Entering Boiler Temperature
°F
09 LAI Leaving Boiler Temperature
°F
10 LAI Tank Temperature
°F
11 LAI Tower Bypass Valve Position 0 – 100%
12 LAI Boiler Bypass Valve Position 0 – 100%
13 LDI Pump Flow/Damper Interlock Switch Open Switch – No Flow
Closed Switch – Flow
14 LAI Secondary Pump 2 Flow 0 = Off
255 = On
15 LAI Secondary Pump 1 Flow 0 = Off
255 = On
16 LAI Loop Pump 1 Flow 0 = Off
255 = On
17 LAI Loop Pump 2 Flow 0 = Off
255 = On
18 LAI Loop Status See Table 2
19 LAI Loop Pump 1 Status 0 = Off
255 = On
20 LAI Loop Pump 2 Status 0 = Off
255 = On
continued on next page...