Data Sheet for Product

Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 4
Document No. 127-0013
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: RMC Monitoring and Control Panel for Self-
Contained Air Conditioning Units
Table 1. RMC Monitoring and Control Panel for Self-Contained Air Conditioning Units.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5046
03 LDI Schedule 1 Status Off/On
04 LDI Schedule 2 Status Off/On
05 LDI Schedule 3 Status Off/On
06 LDI Schedule 4 Status Off/On
07 LAI Group 1 Control Temperature
0 – 255°F
08 LAI Group 2 Control Temperature
0 – 255°F
09 LAI Group 3 Control Temperature
0 – 255°F
10 LAI Group 4 Control Temperature
0 – 255°F
11 LAI Group 1 Static Pressure IWC
12 LAI Group 2 Static Pressure IWC
13 LAI Group 3 Static Pressure IWC
14 LAI Group 4 Static Pressure IWC
15 LAI Group 1 Speed/Vane Position 0 – 100%
16 LAI Group 2 Speed/Vane Position 0 – 100%
17 LAI Group 3 Speed/Vane Position 0 – 100%
18 LAI Group 4 Speed/Vane Position 0 – 100%
19 LAO Number of Units 1 – 8
20 LAO Unit No. 1 Address. This point provides the RMC with its
corresponding level 2 unit’s network address. The address must
match the hex address on the level 2 controller.
1 – 254
21 LAO Unit No. 2 Address. (See Note for Point 20) 1 – 254
22 LAO Unit No. 3 Address. (See Note for Point 20) 1 – 254
continued on next page...