Table 1. Constant Volume, Return Air, Zone Control Rooftop Unit.
Point Type Description Range/Units
91 LAO Network Control Temperature. Uses the network supplied control
temp. (See Points 17 and 48).
40 – 100°F
92 LAO Network Supply Vane Position. Supply vane position controlled to
maintain this point.
0 – 100%
93 LAO Network Watch Dog 1 – 255
94 LAI Fan Operating Hours —
95 LAI Cooling Operating Hours —
96 LAI Heating Operating Hours —
97 LAI Override Operating Hours —
98 LAO Network Outside Air Temperature
-100 – 155°F
99 LDI Device Communication Failure Normal/Failed
Table 2. Control Temperature (Points 17 and 48).
Value Description
0 Return Temperature
1 Space Temperature
2 Network
3 Outside Air Temperature
4 None
Table 3. Unit Status (Point 18).
Value Description
0 Program Inactive
1 Off – Fan Switch
2 Off – Unoccupied
3 Off – Network
4 Off – Manual
5 Off – Service
6 Off – Alarm
7 Calibrate
8 Start Requested
9 Startup Initialize
10 Recirculation
11 Fan On