Data Sheet for Product

Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 6
Document No. 127-0012
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: One-Compressor Screw Chiller
Table 1. One-Compressor Screw Chiller.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5047
03 LAI Circuit 1 Condenser Approach Temperature
0 – 263°F
04 LAI Circuit 1 Condenser Pressure 0 – 450 psi
05 LAI Circuit No.1 Condition at Time of Alarm: Capacity 0 – 100%
06 LAI Circuit No.1 Condition at Time of Alarm: Condenser Leaving Water
Temperature or Outside Air Temperature
-40 – 263°F
07 LAI Circuit No.1 Condition at Time of Alarm: Condenser Pressure 0 – 450 psi
08 LAI Circuit No.1 Condition at Time of Alarm: Evaporator Leaving Water
Temperature
-40 – 263°F
09 LAI Circuit No.1 Condition at Time of Alarm: Evaporator Pressure 0 – 150 psi
10 LAI Circuit No.1 Condition at Time of Alarm: Fan Stage 0 – 6
11 LAI Circuit No.1 Condition at Time of Alarm: Liquid Line Temperature
-40 – 263°F
12 LAI Circuit No.1 Condition at Time of Alarm: Suction Temperature
-40 – 263°F
13 LAI Circuit 1 Alarm See Table 2
14 LAI Circuit 1 Evaporator Pressure 0 – 150 psi
15 LAI Circuit 1 Liquid Line Temperature
-40 – 263°F
16 LAI Circuit 1 Status See Table 3
17 LAI Circuit 1 Subcooling Temperature
0 – 263°F
18 LAI Circuit 1 Suction Temperature
-40 – 263°F
19 LAI Circuit 1 Superheat Temperature
0 – 263°F
20 LAI Compressor 1 Operating Hours Hours
21 LAI Compressor 1 Starts Starts
22 LAI Condenser Entering Water Temperature
-40 – 263°F
23 LAI Condenser Leaving Water Temperature
-40 – 263°F
24 LAI Evaporator Entering Water Temperature
-40 – 263°F