Data Sheet for Product
Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc.  Page 1 of 6 
Document No. 127-0003 
Systems Integration 
APOGEE
¥
 Open Processor with McQuay Microtech 
Driver: Chiller System Controller 
Table 1. Chiller System Controller. 
Point Type  Description  Range/Units 
01  LAO  Device Address  — 
02 LAO Application Number  5059 
03  LAI  Average Chiller Load  0 – 125% 
04  LAI  Chilled Water Loop Pressure Difference  0 – 150 psig 
05  LAI  Chilled Water Return Temperature 
-40 – 263°F 
06  LAI  Chilled Water Supply Temperature 
-40 – 263°F 
07  LAI  Chiller Load Limit – Unit 1  0 – 100% 
08  LAI  Chiller Load Limit – Unit 2  0 – 100% 
09  LAI  Chiller Load Limit – Unit 3  0 – 100% 
10  LAI  Chiller Load Limit – Unit 4  0 – 100% 
11  LAI  Chiller Load Limit – Unit 5  0 – 100% 
12  LAI  Chiller Load Limit – Unit 6  0 – 100% 
13  LAI  Chiller Load Limit – Unit 7  0 – 100% 
14  LAI  Chiller Load Limit – Unit 8  0 – 100% 
15  LAI  Chiller Load Limit – Unit 9  0 – 100% 
16  LAI  Chiller Load Limit – Unit 10  0 – 100% 
17  LAI  Chiller Load Limit – Unit 11  0 – 100% 
18  LAI  Chiller Load Limit – Unit 12  0 – 100% 
19  LAI  Chiller Operating Hours – Unit 1  Hours 
20  LAI  Chiller Operating Hours – Unit 2  Hours 
21  LAI  Chiller Operating Hours – Unit 3  Hours 
22  LAI  Chiller Operating Hours – Unit 4  Hours 
23  LAI  Chiller Operating Hours – Unit 5  Hours 
24  LAI  Chiller Operating Hours – Unit 6  Hours 
25  LAI  Chiller Operating Hours – Unit 7  Hours 
continued on next page...