Data Sheet for Product

Point Map
Rev. 3, February, 2002
Siemens Building Technologies, Inc. Page 1 of 6
Document No. 127-0003
Systems Integration
APOGEE
¥
Open Processor with McQuay Microtech
Driver: Chiller System Controller
Table 1. Chiller System Controller.
Point Type Description Range/Units
01 LAO Device Address
02 LAO Application Number 5059
03 LAI Average Chiller Load 0 – 125%
04 LAI Chilled Water Loop Pressure Difference 0 – 150 psig
05 LAI Chilled Water Return Temperature
-40 – 263°F
06 LAI Chilled Water Supply Temperature
-40 – 263°F
07 LAI Chiller Load Limit – Unit 1 0 – 100%
08 LAI Chiller Load Limit – Unit 2 0 – 100%
09 LAI Chiller Load Limit – Unit 3 0 – 100%
10 LAI Chiller Load Limit – Unit 4 0 – 100%
11 LAI Chiller Load Limit – Unit 5 0 – 100%
12 LAI Chiller Load Limit – Unit 6 0 – 100%
13 LAI Chiller Load Limit – Unit 7 0 – 100%
14 LAI Chiller Load Limit – Unit 8 0 – 100%
15 LAI Chiller Load Limit – Unit 9 0 – 100%
16 LAI Chiller Load Limit – Unit 10 0 – 100%
17 LAI Chiller Load Limit – Unit 11 0 – 100%
18 LAI Chiller Load Limit – Unit 12 0 – 100%
19 LAI Chiller Operating Hours – Unit 1 Hours
20 LAI Chiller Operating Hours – Unit 2 Hours
21 LAI Chiller Operating Hours – Unit 3 Hours
22 LAI Chiller Operating Hours – Unit 4 Hours
23 LAI Chiller Operating Hours – Unit 5 Hours
24 LAI Chiller Operating Hours – Unit 6 Hours
25 LAI Chiller Operating Hours – Unit 7 Hours
continued on next page...