Data Sheet for Product
Page 4 of 6  Siemens Building Technologies, Inc. 
  Document No. 127-0003 
Table 1. Chiller System Controller. 
Point Type  Description  Range/Units 
92  LAO  Tower Stage Set Point – Stage 7 
40 – 100°F 
93  LAO  Tower Stage Set Point – Stage 8 
40 – 100°F 
94  LAO  Tower Stage Set Point – Stage 11 
40 – 100°F 
95  LAO  Tower Stage Set Point – Stage 10 
40 – 100°F 
96  LAO  Tower Stage Set Point – Stage 11 
40 – 100°F 
97  LAO  Tower Stage Set Point – Stage 12 
40 – 100°F 
98  LAO  Tower Valve Set Point 
40 – 100°F 
99  LDI  Device Communication Failure  Normal/Failed 
Table 2. Chiller Status of Units 1 – 12 (Points 32–43). 
Value Description 
0 N/A 
1  Off – Local 
2  Off – Chiller System Controller 
3 Starting 
4 Running 
5 Stopping 
6 Communication Loss 
Table 3. Operating State (Point 47). 
Value Description 
0  Off – Unoccupied 
1  Off – Network 
2  Off – Ambient 
3  Off – Manual 
4  Off – Alarm 
5 Recirculate 
6 Free Cooling 
7  On – Schedule 
8  On – Input 
9  On – Network 
10  On – Manual 