Data Sheet for Product
Siemens Building Technologies, Inc. Page 5 of 6
Document No. 127-0003
Table 4. Current Alarm (Point 50).
Value Description
0 No Alarms
1 – 12 No. 1 – No. 12 Chiller Communications Error
13 Chiller Off – Line Warning
14 Entering Condenser Temperature Sensor Warning
15 Leaving Condenser Temperature Sensor Warning
16 Cooling Tower Failure Warning
17 Chilled Water Pressure Sensor Problem
18 Supply Chilled Water Temperature Sensor Problem
19 Return Chilled Water Temperature Sensor Problem
20 Decoupler Temperature Sensor Problem
21 Outside Air Temperature Sensor Problem
22 Secondary Pump No. 1 Failure Problem
23 Secondary Pump No. 2 Failure Problem
24 Secondary Pump No. 3 Failure Problem
25 Secondary Pump No. 4 Failure Problem
26 Secondary Pump No. 5 Failure Problem
27 Secondary Pump No. 6 Failure Problem
28 Decoupler Flow Sensor Problem
29 No Secondary Chilled Water Flow Fault
30 Entering Condenser Temperature Sensor Fault
31 Leaving Condenser Temperature Sensor Fault